Overheating Analysis Methods
Different overheating analysis methods are used depending on the sector, but all are based on the CIBSE TM52 methodology.
TM52 is based on BS EN 15251, which uses field research to define ‘adaptive comfort’. It makes allowances for changing occupant behaviour and is now recognised as the standard approach.
There are three criteria that need to be satisfied to meet TM52:
Criterion 1: This is a limit on the number of hours the operative temperature is above the upper limit of the comfort temperature. The hours of exceedance (∆T ≥ 1K shall not be more that 3% of occupied periods during the period May to September.
Criterion 2: Daily weighted exceedance. This is a limit on the degree of overheating in any given one day of the simulation period. It must be less than or equal to 6.
Criterion 3: Absolute upper limit. This is an absolute temperature limit above the upper comfort temperature, beyond which normal adaptive actions will be insufficient to prevent discomfort. The value shall not exceed 4K.
We can offer the following types of overheating analysis, depending on your project:
Different overheating analysis methods are used depending on the sector, but all are based on the CIBSE TM52 methodology.
TM52 is based on BS EN 15251, which uses field research to define ‘adaptive comfort’. It makes allowances for changing occupant behaviour and is now recognised as the standard approach.
There are three criteria that need to be satisfied to meet TM52:
Criterion 1: This is a limit on the number of hours the operative temperature is above the upper limit of the comfort temperature. The hours of exceedance (∆T ≥ 1K shall not be more that 3% of occupied periods during the period May to September.
Criterion 2: Daily weighted exceedance. This is a limit on the degree of overheating in any given one day of the simulation period. It must be less than or equal to 6.
Criterion 3: Absolute upper limit. This is an absolute temperature limit above the upper comfort temperature, beyond which normal adaptive actions will be insufficient to prevent discomfort. The value shall not exceed 4K.
We can offer the following types of overheating analysis, depending on your project:
- TM52, which is generally used for non-residential buildings (residential buildings now require assessment against TM59).
- TM59 (either by the simplified or detailed method), which is required for all residential new build and major refurbishment projects. See here for more details.
- BB101, which is specifically for school buildings.
- BREEAM Hea04 - Thermal Comfort.